Mitsubishi MELSEC AJ65BT-R2 User Manual page 29

Rs-232c interface module type
Hide thumbs Also See for MELSEC AJ65BT-R2:
Table of Contents

Advertisement

3 SPECIFICATIONS
Device No.
Signal name
OS reception area
RXn6
clear complete
EEPROM function
RXn7
normal complete
EEPROM function
RXn8
error complete
CS (CTS)
RXn9
signal
Signal
DR (DSR)
RXnA
status
signal
RXnB
CD signal
RXnC
General-purpose
external input signal
RXnD
Initial data read
RX(n+1)9
complete
The OS reception area clear request (RYn6) is turned ON to abort the data in the R2
OS reception area.
When OS reception area clear is completed, the R2 turns the OS reception area clear
complete (RXn6) ON, so the OS reception area clear request (RYn6) will turn OFF.
OS reception area
clear request
(RYn6)
OS reception area
clear complete (RXn6)
When the R2 EEPROM function is executed, after the data is read into the R2 buffer
memory (1C0
), EEPROM function request (RYn7) turns ON.
H
When completed normally, EEPROM function normal complete (RXn7) turns ON.
When completed abnormally, EEPROM function error complete (RXn8) turns ON.
When these signals turn ON, EEPROM function request (RYn7) turns OFF.
EEPROM function request (RYn7)
EEPROM function normal complete
or EEPROM function error complete
This signal indicates the control signal status (CS, DR, CD signal) during RS-232-C
communication with an ON or OFF state.
This signal indicates the status of the R2 general-purpose external input (XC, XD)
status with an ON or OFF state.
RXnC: Corresponds to XC
When writing in the initialization data before executing initialization, the initial data read
request (RY(N+1)9) turns ON, and the initialization data is written to the master station.
At this time, remote station ready (RX(n+1)B) turns OFF.
When the writing is completed, initial data read complete (RX(n+1)9) turns ON, and
the initial data read request (RY(n+1)9) turns OFF.
When these turn OFF, initial data read complete (RX(n+1)9) turns OFF, and remote
station ready (RX(n+1)B) turns ON.
Initial data read request (RY(n+1)9)
Initial data read complete
(RX(n+1)9)
Remote station ready (RX(n+1)B)
3 - 9
Details
R2 clears the OS
reception area.
R2 executes
EEPROM function.
(RXn7)
(RXn8)
RXnD: corresponds to XD
R2 writes initialization
data to master station.
MELSEC-A