Drive Parameter Registers (Read/Write); Table 5-4 Drive Parameters - YASKAWA GPD 315/V7 Technical Manual

Modbus rtu
Hide thumbs Also See for GPD 315/V7:
Table of Contents

Advertisement

Drive Parameter Registers (Read/Write)

Parameter
ADDR
Password /
n001
0101h
Initialization
n002
0102h
Operation
n003
0103h
Reference
n004
0104h
Selection
n005
0105h
Stop Method
Reverse
n006
0106h
Prohibit
Stop Key
n007
0107h
Function
Frequency
n008
0108h
Reference
Selection Local
Freq. Ref.
n009
0109h
Enter Req.
Operator
n010
010Ah
Connection
Detection
Max. Output
n011
010Bh
Frequency
n012
010Ch
Max. Voltage
Freq. @ Max.
n013
010Dh
Voltage
GPD315/V7 Modbus RTU Technical Manual TM 4325

Table 5-4 Drive Parameters

Name
Set
0
N001 Can Be Read And Set; N002-N179 Others Read Only
1
N001-N039 Can Be Read And Set
2
N001-N067 Can Be Read And Set
3
N001-N113 Can Be Read And Set
4
N001-N179 Can Be Read And Set
5
Not Used
6
Clear Fault Record Only
7
Not Used
8
2-Wire Initialization
9
3-Wire Initialization
10
2-Wire Initialization (Us)
11
3-Wire Initialization (Us)
12
2-Wire Initialization (European)
13
3-Wire Initialization (European)
15
All Parameters Can Be Read And Set
20
Initialize All Parameters To Factory Defaults
Control
0
V/F Control
Method
1
Open Loop Vector
0
Digital Operator
1
Terminal
Method
2
Serial Communication
3
Option PCB
0
Digital Operator Pot
1
Frequency Reference 1 (N024)
2
Voltage Reference (0-10v)
3
Current Reference (4-20 Ma)
4
Current Reference (0-20 Ma)
5
Pulse Train Reference
6
Serial Communication (Address 002h)
7
Option PCB
0
Ramp To Stop
1
Coast To Stop
0
Reverse Run Enabled
1
Reverse Run Disabled
0
Stop Key Enabled.
1
Stop Key Is Active Only When N003 Is Set From Digital Operator
0
Frequency Ref. From Digital Operator Pot
1
Frequency Ref. From N024
0
Enter Required To Accept
1
Enter Not Required To Accept
0
Disabled
1
Enabled (Operator Connection Fault Detect)
50.0 - 400.0Hz
0.1 - 255.0 (230V Drive)
0.2 - 510.0 (460 V Drive)
0.2 - 400.0Hz
Description
1
1
(Parameters n180 – n210 re not initialized)
(Parameters n180 – n210 re not initialized)
(Parameters n180 – n210 re not initialized)
(Parameters n180 – n210 re not initialized)
4
4
(initialized only by n001 set to 10 or 11)
(initialized only by n001 set to 10 or 11)
4
4
Default
1
0
1
2
0
0
0
0
0
0
60.0
230
460
60
23
Page