Chapter 5; Parameter Tables; Simultaneous Broadcast Registers (Write Only); Command Registers (Read/Write) - YASKAWA GPD 315/V7 Technical Manual

Modbus rtu
Hide thumbs Also See for GPD 315/V7:
Table of Contents

Advertisement

Simultaneous Broadcast Registers (Write Only)

Register
Name
Operation
0001h
Signals
002h
Frequency Reference

Command Registers (Read/Write)

Register
Name
0000h
Reserved
Operation
0001h
Signals
0002h
Frequency Reference
0003h
V/f Gain
0004h – 0008h
Reserved
0009h
000A – 001Fh
Reserved
GPD315/V7 Modbus RTU Technical Manual TM 4325

Chapter 5

Parameter Tables

Table 5-1 Simultaneous Broadcast Registers

Bit
Description
0
Run Command
1
Direction Command
1
2
Not Used
1
3
Not Used
4
External Fault
5
Fault Reset
1
6
Not Used
1
7
Not Used
1
8 - F
Not Used
2

Table 5-2 Command Registers

Bit
Description
0
Run Command
1
Direction Command
2
External Fault
3
Fault Reset
4
Multi-function Input Reference 1
5
Multi-function Input Reference 2
6
Multi-function Input Reference 3
7
Multi-function Input Reference 4
8
Multi-function Input Reference 5
9
Multi-function Input Reference 6
A
Multi-function Input Reference 7
1
B - F
Not Used
2
(1000/100%)
3
0
Multi-function Output 1
1
Multi-function Output 2
2
Multi-function Output 3
1
3 - F
Not Used
3
1: Run
1: Reverse
1: Fault (EF0)
1: Fault Reset
1: Run
1: Reverse
1: Fault (EF0)
1: Fault Reset
(Function selection by n050)
(Function selection by n051)
(Function selection by n052)
(Function selection by n053)
(Function selection by n054)
(Function selection by n055)
(Function selection by n056)
2.0% - 200.0%
(Enabled when n057 = 18)
(Enabled when n058 = 18)
(Enabled when n059 = 18)
0: Stop
0: Forward
0: Stop
0: Forward
1: Contact ON
1: Photo coupler 1 ON
1: Photo coupler 2 ON