18.

Applications

18.1
RAMP & SOAK
RAMP:
I.
SET2.1=1
To display AL3
II.
SET4.1=1
To display ALD3
III. ALD3=9
Open RAMP option
IV. Then, AL3 will not display. It was replaced by RAMP.
RAMP
0 0.0 0
SOAK :
I.
ALD1 / ALD2=19
II.
AL1 / AL2 will display as below:
AL1
0 0 . 0 0
Example :
SV=100 ℃ ,RAMP=10.00 ( /min)
100℃
SV=PV (When start RAMP function)
PV=25℃
Power on
5 seccons(Start RAMP function)
All manuals and user guides at all-guides.com
Range:00.00 ~ 99.99(℃/ min)
(If RAMP is not used,please set
ALD3 to 0)
To use Sock Timer.
Range:00.00 ~ 99.59(Hour.Minute)
,AL1=00.10 min,PV=25 ℃
Time on
if PV > = SV(100℃)
SV=SV+RAMP
52
Time up
AL1 on
AL1
00.01
Sock Timer
00.10
00.10
counts
1sec.