38MGRBQ: Service Manual
DC Fan Motor (Control Chip is in PCB)
Release the UVW connector. Measure the U-V, U-W, and V-W resistance. If the resistances are not equal to each other, the fan motor may be
experiencing problems and needs to be replaced. Otherwise, the PCB must have an issue and needs to be replaced.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
59