Carrier 38MGRBQ18B-3 Service Manual page 51

Multi-zone outdoor unit ductless system sizes 18r, 24hh, 30hh, 36r, 36hh, 48r and 48hh
Table of Contents

Advertisement

38MGRBQ: Service Manual
DIAGNOSIS AND SOLUTION (CONT)
E4/EC 50 (Outdoor temperature sensor (coil sensor T3,ambient sensor T4, Compressor discharge sensor
T5? A indoor coil outlet pipe sensor T2B) malfunction) diagnosis and solution
F1/F2/F3/F4/F5 (No.A,B,C,D,E Indoor unit coil outlet temp. sensor malfunction) diagnosis and solution
Outdoor room temperature sensor T4 is in open circuit or has short circuited (EC 53)
Compressor discharge temperature sensor T5 is in open circuit or has short circuited (EC 54)
Evaporator coil outlet temperature sensor T2B is in open circuit or has short circuited (EC 56)
ERROR CODE
MALFUNCTION DECISION
CONDITIONS
SUPPOSED CAUSES
Troubleshooting
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
E4/F1/F2/F3/F4/F5/ EC 52/EC 53/EC 54/EC 56/EC 50
If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the failure.
Wiring mistake
Faulty Sensor
PCB faulty
Check the connections
between temperature
sensor and PCB. Are
the connections good?
Yes
Check the resistance value
of the sensor via Appendix 1
and Appendix 2
Is it normal?
No
Replace the sensor
No
Correct the connections.
Yes
Replace indoor or outdoor PCB.
51