GENERAL BLOCK
INFORMATION

Device Description

Node Address

Modes

4-2
Before configuring the device, ensure the host has the appropriate Device
Description file revision for this device. The device descriptor can be found on
www.rosemount.com. The initial release of the Rosemount 3144P with
F
fieldbus protocol is device revision 1.
OUNDATION
The transmitter is shipped at a temporary (248) address. This will enable
F
fieldbus host systems to automatically recognize the device and
OUNDATION
move it to a permanent address.
The Resource, Transducer, and all function blocks in the device have modes
of operation. These modes govern the operation of the block. Every block
supports both automatic (AUTO) and out of service (OOS) modes. Other
modes may also be supported.
Changing Modes
To change the operating mode, set the MODE_BLK.TARGET to the desired
mode. After a short delay, the parameter MODE_BLOCK.ACTUAL should
reflect the mode change if the block is operating properly.
Permitted Modes
It is possible to prevent unauthorized changes to the operating mode of a
block. To do this, configure MODE_BLOCK.PERMITTED to allow only the
desired operating modes. It is recommended to always select OOS as one of
the permitted modes.
Types of Modes
For the procedures described in this manual, it will be helpful to understand
the following modes:
AUTO
The functions performed by the block will execute. If the block has any
outputs, these will continue to update. This is typically the normal
operating mode.
Out of Service (OOS)
The functions performed by the block will not execute. If the block has any
outputs, these will typically not update and the status of any values passed
to downstream blocks will be "BAD". To make some changes to the
configuration of the block, change the mode of the block to OOS. When
the changes are complete, change the mode back to AUTO.
MAN
In this mode, variables that are passed out of the block can be manually
set for testing or override purposes.
Other Types of Modes
Other types of modes are Cas, RCas, ROut, IMan and LOW. Some of
these may be supported by different function blocks in the 3144P. For
more information, see the Function Block manual (document number
00809-0100-4783).