Condensate Drain Piping - Trane 2TEE3F39A1000A Installer's Manual

Convertible variable speed – air handlers 3.5 - 5 ton
Table of Contents

Advertisement

BRAZE SHIELD
Figure 16
F. BRAZING TO EVAPORATOR SECTION
NOTE: A brazing shield is provided in the information
pack accompanying this unit. This shield fits over the
refrigerant fittings while brazing. Wet the shield before
brazing. See Figure 16.
IMPORTANT:
Do NOT unseal refrigerant tubing until ready to cut and
fit refrigerant lines.
1. Remove both sealing caps from indoor coil.
2. Field supplied tubing should be cut squared-off, en-
suring the tube is still round and free of burrs at
the connecting end. Clean the tubing to prevent
contaminants from entering the system.
3. Run refrigerant tubing into the stub sockets of in-
door unit coil. Refrigerant line openings must be
completely sealed.
4. Braze and evacuate according to indoor and outdoor
installation instructions.
5. Seal around refrigerant lines.
PAINTED AREAS OF UNIT MUST BE SHIELDED
DURING BRAZING
G. CONDENSATE DRAIN PIPING
NOTE: Make certain that the unit has been installed in a
level position to ensure proper draining.
The indoor blower is downstream of the evaporator coil
which creates a negative pressure at the condensate
drain connections during operation. The condensate
drain connections in front of the indoor coil are 3/4"
NPT. The lower connection is the primary drain. See
Figure 17.
Two secondary drain connections are provided for the
different orientations (See Figure 17). The lower of the
two should be connected as a backup to prevent conden-
sate overflow by a blocked primary drain.
3/4" NPT Secondary
drain connection
For proper drainage of condensate, the following steps
should be followed:
1. The primary drain line must be trapped with a
minimum of 2" water seal as shown in Figures 17 &
18. Do not use preformed 3/4" PVC running
traps.
The use of Field fabricated or manufactured traps
as shown in Figures 18 & 19 is acceptable. The
manufactured trap shown in Figure 18 allows for a
float switch option to be added.
Refer to the manufacturers data and instructions
for details.
Manufactured traps
EZT-105
Figure 17
3/4" NPT Primary
drain connection
2" MINIMUM
2" MINIMUM
Figure 18