Trane 2TEE3F39A1000A Installer's Manual page 5

Convertible variable speed – air handlers 3.5 - 5 ton
Table of Contents

Advertisement

NOTE: Installation of the downflow baffle kit included
with unit is required on downflow applications. See
Figure 9.
c. Remove front shield by removing screws on
right side. Make sure to reinstall front shield af-
ter baffle changes. See Figure 9.
d. Remove the front triangular baffle from the coil
and install the 1/2" wide gasket provided per Fig-
ure 9. Trim the gasket length to fit the baffle. Re-
install the baffle to coil, with gasket material
compressed against the coil.
e. Install the water blow-off baffles provided on each
side of the coil with the flange at the top as
shown in Figure 9. The bottom of the baffle is to
be as close to the bottom of the coil as possible.
f. Install the 7/8" wide gasket in each side of the
drain pan as shown in Figure 9 (sect. X-X).
g. The 5 ton model (2/4TEE3D62) requires 2 water
diverter baffles to be placed underneath the coil
on the inside edge of the drain pan. See Figure 9.
DOWNFLOW BAFFLE KIT
SCREWS TO
REMOVE COIL
7/8" GASKET
SECT. X-X
(TYP. BOTH SIDES)
BLOW-OFF
ATTACH WITH
18-GE12D1-5
7/8" GASKET
X
1/2" GASKET
INSIDE SURFACE
OF BAFFLE
WATER
BAFFLES
2 SCREWS
EACH SIDE
Fill the bend in the baffle which fits the inner
edge of the drain pan with RTV type adhesive/
sealant before installing the baffle.
h. The unit is then placed with the blower side
down and the coil is replaced on the coil channel
supports with the drain connections at the bot-
tom. The unit is now in downflow position with
front access. Do not reattach coil support tab.
For Maximum Efficiency on
X
WATER
DIVERTER
BAFFLES
(5-ton only)
FILL WITH SEALANT
Installer's Guide
Horizontal Left,
Upflow and Downflow
Remove
and
Discard
Figure 8
DISCARD
DRIP TRAY
SCREWS TO
REMOVE COIL
Figure 9
Replace
with
Narrow
Baffle
5