Active Interface Modules; Description - Siemens SINAMICS S120 Equipment Manual

Chassis power units liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-Side Power Components

2.3 Active Interface Modules

2.3
Active Interface Modules
2.3.1

Description

Active Interface Modules are used in conjunction with the Active Line Modules in chassis
format. Active Interface Modules contain a Clean Power Filter with basic RI suppression, the
pre-charging circuit for the Active Line Module, the line voltage sensing circuit and
monitoring sensors.
Frame size GI is equipped as standard with a bypass contactor which ensures a highly
compact design. The bypass contactor must be provided separately for frame sizes HI and
JI.
The vast majority of line harmonics are suppressed by the Clean Power Filter.
The Active Interface Module contains:
• Clean Power Filter
• Line reactor
• Pre-charging circuit
• Bypass contactor (for frame size GI)
• Voltage sensing module (VSM)
• Fan
Fig. 2-3
2-8
Active Interface Module
SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4
Chassis Power Units Liquid Cooled