Recommended Clearances; Unit Isolation; Direct Mounting; Neoprene Isolator Mounting - Trane CGWF Installation Operation & Maintenance

Scroll liquid chillers
Hide thumbs Also See for CGWF:
Table of Contents

Advertisement

3
CGWF/CCAF
1
Figure 6
Isolators and Locations
22
Installation Mechanical

Recommended Clearances

Provide recommended access clearance for service and maintenance operations.
Refer to recommendations provided in Figure 7 - Figure 11. Local codes may take
precedence over recommendations.

Unit Isolation

There are two mounting methods that will minimize sound and vibration. They are the
direct-mount method and the isolator-mount method.

Direct Mounting

The unit can be direct-mounted on an isolated concrete pad or on an isolated concrete
footing at each end. Refer to Table 3 and Table 4 for unit operating weights. A
mounting hole is provided in the base of the unit frame at each mounting location.
Provide a means of securely anchoring the unit to the mounting surface. Level the
unit carefully. Refer to "Leveling the Unit" .

Neoprene Isolator Mounting

Install the optional neoprene mounting isolators at each mounting location. Refer to
Table 6 for isolator selection, placement and loading information. Isolators are
identified by color and by the isolator part number.
Bolt the isolator to the mounting surface. Do not fully tighten the mounting bolts.
Mount the unit on the isolators and install a 1/2-inch (13 mm) nut on each isolator
positioning pin. Maximum isolator deflection should be 1/4-inch. Level the unit
carefully. Refer to "Unit Leveling" . Now fully tighten isolator mounting bolts.

Neoprene Isolator Data

4
2
Control
Panel End
Table 6
RDP 3 Neoprene Isolator Selection
Unit Size
1
20
Green
25
Green
30
Green
40
Gray
50
Gray
60
Gray
Location
2
3
CGWF
Green
Green
Green
Green
Green
Green
Gray
Gray
Gray
Gray
Gray
Gray
CCAF
4
Green
Green
Green
Gray
Gray
Gray
CGWF-SVX01A-EN