Appliance Location And Clearances To Combustibles - Heatilator RAVE32-IFT-B Installation Manual

Hide thumbs Also See for RAVE32-IFT-B:
Table of Contents

Advertisement

B. Appliance Location and Clearances to
Combustibles
When selecting a location for the appliance it is important
to consider the required clearances to walls and allow suf-
ficient clearance for heat management systems venting.
See Figure 3.6.
WARNING! Risk of Fire or Burns! Provide adequate
clearance around air openings and for service access.
Due to high temperatures, the appliance should be lo-
cated out of traffic and away from furniture and draperies.
E
1/2 IN.
A
Note: Adjust framing dimensions for interior chase sheathing (such as sheetrock).
Inches
RAVE32-IFT-B
Millimeters
Inches
RAVE36-IFT-B
Millimeters
Inches
RAVE42-IFT-B
Millimeters
Figure 3.6 Appliance Locations
Heatilator • RAVE32-IFT-B, RAVE36-IFT-B, RAVE42-IFT-B Installation Manual • 2619-983 Rev. U • 9/22
14
A
C
TOP VENT
ONE 90
ELBOW
0
It is acceptable to install the Passive Heat Front Discharge Kit
with a corner installation.
Refer to Section 10.C for mantel and wall
projection information.
Consider the mantel or cabinet system to be
installed and comply with the necessary
requirements for elevated hearth. Refer to
instructions included with cabinet system.
A
B
42-7/8
37
60-5/8
1089
940
46-3/8
42
65-1/2
1178
1067
51-3/8
49
72-5/8
1305
1245
NOTICE: Illustrations reflect typical installations and are
FOR DESIGN PURPOSES ONLY. Illustrations/diagrams
are not drawn to scale. Actual installation may vary due to
individual design preference.
D*
ALCOVE
INSTALLATION
TOP VENT
ONE 90° ELBOW
B
C
1541
See Section 10.C for Alcove Installation
(Mantel and Wall Projection).
1664
1845
18 in. (457 mm) required
when Passive Heat Side
Discharge Kit is installed.
F
D
14-5/8
16-3/8
18-3/4
E
F
17-1/4
371
438
17-1/4
416
438
17-1/4
476
438