4.2

Device status icons

For a complete list of the device status icons that appear on the LCD display, as well as what
they mean, please refer to the Diagnosing and Troubleshooting section of the full operating
instructions.
4.3

Connecting SITRANS LR560

Note
• Check the device label on your instrument, to verify the approval rating.
• Use appropriate conduit seals to maintain IP or NEMA rating.
• Use twisted pair cable: AWG 22 to 14 (0.34 mm² to 2.5 mm²).
• Separate cables and conduits may be required to conform to standard instrumentation
wiring practices or electrical codes.
1. Loosen locking screw.
2. Remove LR560 lid.
3. Remove optional display by gently turning the display a quarter turn counter-clockwise until
it is free.
4. Strip the cable jacket for approximately 70 mm (2.75") from the end of the cable.
5. Thread the wires through the gland
6. Strip/remove conductor jacket to 8mm from end.
7. Connect the wires to the terminals as shown: the polarity is identified on the terminal block.
8. Tighten screws on Terminal Block. Suggested screw torque: 7.0 lb-in.
9. Ground the instrument according to local regulations.
10.Tighten the gland to form a good seal.
11.Replace optional display and device lid.
12.Tighten locking screw.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof
1)
applications.
SITRANS LR560
Compact Operating Instructions, 02/2022, A5E39693895-AC
.
1)
Connecting
4.2 Device status icons
25