Commissioning
5.5 Commissioning via handheld programmer
Response rate
Factory setting:
Setting range:
Purpose:
Description:
Units
Factory setting:
Setting range:
Purpose:
42
Parameter view
MED
Response rate Fill rate per Minute/Empty rate
SLOW
MED
FAST
Sets the reaction speed of the device to measurement changes in the tar-
get range. Selecting SLOW changes setting for AVERAGE AMOUNT to 0.9.
Use a setting just faster than the maximum vessel filling or vessel empty-
ing rate (whichever is greater).
Parameter view
m
m, cm, mm, ft, in
Sensor measurement units.
Parameter view
per Minute
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
Compact Operating Instructions, 02/2022, A5E39693895-AC
Edit mode
Damping Filter
600 s
60 s
0 s
Edit mode
Edit mode
SITRANS LR560