Installation - Fiaecon102 - Trane FIAECON102 Series Installation Instructions Manual

Low leak economizer, packaged rooftop units 6 to 25 tons with symbio
Table of Contents

Advertisement

Installation - FIAECON102*

WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could
result in death or serious injury. Disconnect all electric
power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized.
1. Remove the existing economizer hood end panel (factory
installed) from the unit and discard (see
Figure 1.
Economizer
Filler Panel
Hood Triangle
Hood Top
FA Hood Front
Support
FA Hood Mist Eliminator
Side Retainer (2 Places)
FA Hood Mist Eliminator
Rear Blockoff
Mist Eliminator
Dimples for Powered
Exhaust Screws
Barometric Relief
Hood
2. Apply 1-inch gasket material to disassembled unit. See
Figure
2.
Figure 2.
Gasket material position
Corners of RTJ
6
and Economizer
Top of Filler
3
Panel
2
4
Top of
Economizer
Top of
Hood Triangle
Barometric
1
Relief Hood
Seal between
Economizer and Unit
6
Figure
1).
4
5
1
Table 2.
Parts list
Item
1
Unit - seal between economizer and unit
Top of economizer - seal between economizer and top of unit or
2
between economizer and top filler panel
3
Between top of filler panel and unit only if filler panel is required
4
Top of hood triangle - seal between hood and hood flange
Around barometric relief hood - seal between barometric relief hood
5
Apply 1-inch gasket in corners to seal area between RTU unit and
6
3. Remove the hood top from the non-linkage side of the
economizer and set aside for
4. Install economizer in the unit, shift left, and install single
screw into alignment holes.
Note: Screw will be removed later.
5. Use self-drilling screws through remaining large holes
around perimeter of economizer.
6. Remove alignment screw.
Figure 3.
Pictorial layout of previous steps
Insert economizer fully
then shift left all the way
Alignment
screw
Shift Left
Remove screw holding
Self-drilling screws
barometric relief blade
around perimeter
7. Assemble flange to hood top (removed in
hood triangles and attach to economizer. See
p.
7.
8. Install mist eliminator into hood assembly and secure with
filter clips provided on hood top.
9. Install filler panel above hood if necessary (does not apply
to all models).
10. Remove shipping screw from aluminum barometric relief
blade.
11. If a powered exhaust will be installed go to
Exhaust," p.
7.
12. Assemble and install barometric relief hood.
Description
and unit
economizer
Step
7.
Step
3), then to
Figure 4,
"Powered
ACC-SVN264B-EN