Empire Comfort Systems DVCT36CBP Installation Instructions Manual page 20

Direct vent zero clearance gas fireplace heater
Table of Contents

Advertisement

Horizontal vent Clearance
For horizontal vent, maintain 1 inch of clearance to the bottom
and sides of vent, and 3 inches of clearance to combustibles
above the vent pipe. See Figure 36.
vertical vent Clearance
For vertical vent, maintain a minimum 1 of inch clearance to
combustibles.
NOTICE: maintain 1 of inch of clearance to combustibles around
vertical vent pipe. See Figure 35. For horizontal vent systems,
maintain a minimum 1 inch of clearance from the bottom and sides
of the vent to combustibles and a 3 inches of
vent pipe
to combustibles. See Figures 35 and 36.
VENT PIPE
TOP OF VENT
3" (76 mm)
1" (25 mm)
Horizontal vent Clearances - Figure 36
Page 20
INSTALLATION (CONT'D)
clearance above the
1" MINIMUM CLEARANCE
AROUND VENT PIPE
Figure 35
COMBUSTIBLES NOT
ALLOWED IN SHADED
AREA
5" DIAMETER FLUE
8" DIAMETER
INTAKE VENT
1" (25 mm)
ATTENTION: Cold climate installation recommendation: When
installing this unit against an exterior wall, the exterior wall must
be insulated to conform to applicable insulation codes. The
fireplace outer wrapper is not considered a thermal barrier and
can allow air infiltration. Care should be taken to properly seal
the chase area so air infiltration is kept to a minimum and drafts
do not occur through the fireplace.
vent Runs
In planning the installation, you must install certain components
before the fireplace is secured in position. These include the
direct-vent system, gas piping, and the electrical wiring.
The appliance can be mounted on any of the following surfaces:
1.
A flat, hard combustible or non-combustible surface.
2.
A raised wooden platform.
3.
Four corner supports(such as masonry blocks). These supports
must be positioned so they contact all four perimeter edges on
the bottom of the unit.
38745-4-0319