6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
6.2.4 Configuring the S3M25-100K UPS and Optimizing Charging of
the BP240V65/V65L and BP240V100/V100L Battery Cabinets
Step 1: Setting the Battery Group
The Battery Group is Quantity 1 for every set of 20 batteries that are in and/or connected to the UPS model. For example, UPS
model S3M20K-NIB has no internal batteries and is Battery Group 1 by default for any UPS model. However, to connect a
BP240V65 cabinet with 20 internal batteries to the S3M20K-NIB, the S3M20K-NIB UPS must remain set to Battery Group 1
(one set of 20 batteries). However, to connect a second BP240V65 to the S3M20K-NIB UPS, the UPS Battery Group must be
2 (two sets of 20 batteries). Obtain the Battery Group number based on the specific S3M UPS and Battery Cabinet models
combination from the chart under Section 6.4.
The value can be 1 to 8. The default value is 1 for S3M UPS models without internal batteries.
Step 2: Setting the Battery Number
The battery number must remain at 20 for all S3M10-100K UPS models when connected to Tripp Lite external battery
cabinets designed for the S3M-Series UPS Series.
Step 3: Setting Single Battery (Ah) Capability
Change the Single Battery (Ah) Capability to the individual Ah capacity for one individual battery as follows for the specific
battery cabinet models:
• BP240V09/BP240V09K: the Single Battery (Ah) Capacity is 9
• BP240V40/BP240V40L: the Single Battery (Ah) Capacity is 40
• BP240V65/BP240V65L: the Single Battery (Ah) Capacity is 65
• BP240V100/BP240100L: the Single Battery (Ah) Capacity is 100
The values can be 7~2000.
Scroll to the next display screen by pressing the down arrow.