5. Installation
5.5.2 Battery Installation and Connection
The 40 batteries can be divided into two groups connected in parallel for use. Each group has 20 batteries in series
(BAT+, N and BAT-). Place the batteries in the cabinet from the bottom to top one-by-one, then connect the battery cables
according to the diagrams that follow.
Note: The positive and negative polarity of the battery cannot be reversed or short circuited. Doing so will damage the battery and/or cause
injury. Do not touch the battery's positive and negative terminals at the same time. Before replacing or removing the batteries, disconnect
the breaker, pull up cell terminals and remove the screws of the copper bus bar. Not following the instructions could result in damage to the
equipment or personal injury. The installation must consist of 40 batteries.
Layer 4
Layer 3
Layer 2
Layer 1
Figure 5-25A: Front view
33
Battery Group 2
Battery Group 1