2-41. E: A8. Refrigerant leakage sensor error (Indoor unit)
Indicator
Indoor unit
Detective actuator
Forecast of cause
Check point 1. Refrigerant leakage detection conditions
•
When the refrigerant leakage sensor detects refrigerant.
•
System stop -> Cooling/heating cannot be operated.
•
Stir operation by fan -> Safety is important, and fan operation cannot be stopped.
-> Check for refrigerant leaks and take corrective action.
Check point 2. Error release condition
Power on again.
•
If the power is not turned on again, the error will not be cleared even if the gas concentration
drops.
•
If the refrigerant leakage is detected again after the power is turned on again, an error will occur
again.
•
Replace the refrigerant leakage sensor as it will not recover if exposed to a high concentration
of gas or if exposed multiple times even if the concentration is not high.
2-41. E: A8. Refrigerant leakage sensor error (Indoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
↓
↓
End
- (03-57) -
10 time flash
8 time flash
Continuous flash
E: A8
Refrigerant leakage sensor
Refrigerant leakage
2. Troubleshooting with error code