Fujitsu AUXG07KVLA Manual page 193

2-unit multi-split type
Hide thumbs Also See for AUXG07KVLA:
Table of Contents

Advertisement

2-16. E: 45. Refrigerant leakage sensor error (Indoor unit)
Indicator
Indoor unit
Detective actuator
Refrigerant leakage sensor
Forecast of cause
System is down.
Check point 1. Check connection of connector
Check if connector is loose or removed.
Check erroneous connection.
Check if refregerant leakage sensor cable is open.
-> Reset power when reinstalling due to removed connector or incorrect wiring.
Check point 2. Replace refrigerant leakage sensor
If an abnormality (failure) occurs, the refrigerant leakage sensor needs to be replaced.
2-16. E: 45. Refrigerant leakage sensor error (Indoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
When refrigerant leakage sensor open, short circuit, or
abnormal voltage of drive circuits detected.
End
- (03-29) -
4 time flash
5 time flash
Continuous flash
E: 45
Connector connection failure
Harness disconnection
Refrigerant leakage sensor deterioration
2. Troubleshooting with error code

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents