2-3. E: 12. Wired remote controller communication error (Indoor
unit)
Indicator
Indoor unit
Indoor unit
Detective actuator
Wired remote control
Forecast of cause
Check point 1. Check the connection of terminal
After turning off the power, check & correct the followings.
Check the connection of terminal between wired remote controller and indoor unit, and check if
there is a disconnection of the cable.
Check Point 1-2 : Check the wired remote controller and main PCB
[Compact cassette and floor types]
Check voltage at CN14 (terminal 1—3, terminal 1—2) of main PCB. (Power supply to the remote
controller)
If it is DC 12 V, the remote controller is failure. (Main PCB is normal)
Replace the remote control
If it is DC 0 V, the main PCB is failure. (Check remote controller once again)
Replace the main PCB
[Wall mount type for KGTB, KGTE, KMCE, KETA, KETE]
Check voltage at CN300 (terminal 1—2) of main PCB or communication PCB. (Power supply to the
remote controller)
If it is DC 12 V, the remote controller is failure. (Main PCB is normal)
Replace the remote control
If it is DC 0 V, the main PCB is failure. (Check remote controller once again)
Replace the main PCB
[Wall mount type for KMTB, KMCC]
Check voltage at CNC01 (terminal 1—3) of main PCB or communication PCB. (Power supply to the
remote controller)
If it is DC 13 V, the remote controller is failure. (Main PCB is normal)
Replace the remote control
If it is DC 0 V, the main PCB is failure. (Check remote controller once again)
Replace the main PCB
[Mini duct and Slim duct types]
Check voltage at CN300 (terminal 1—3, terminal 1—2) of main PCB. (Power supply to the remote
controller)
If it is DC 12 V, the remote controller is failure. (Main PCB is normal)
Replace the remote control
If it is DC 0 V, the main PCB is failure. (Check remote controller once again)
Replace the main PCB
2-3. E: 12. Wired remote controller communication error (Indoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
Main PCB
- (03-15) -
1 time flash
2 time flash
Continuous flash
When the indoor unit cannot receive the signal from
wired remote controller more than 1 minute during
normal operation.
Terminal connection abnormal
Wired remote control failure
Main PCB failure
E: 12