Fujitsu AUXG07KVLA Manual page 198

2-unit multi-split type
Hide thumbs Also See for AUXG07KVLA:
Table of Contents

Advertisement

2-21. E: 57. Damper (Open/Close) simultaneous detection limit
switch error (Indoor unit)
Indicator
Indoor unit
Indoor unit main PCB
Detective actuator
Limit switch
Forecast of cause
Check point 1. Check limit switch
Check operation of limit switch. (any blocking by dust, etc.)
Remove limit switch and check ON/OFF switching operation by using a meter.
-> If limit switch is detective, replace it.
Check point 2. Check connector (CN18)/wire
Check loose contact of CN18/shorted wire (pinched wire).
-> Replace limit switch if the wire is abnormal
Check point 3. Replace the main PCB
If Check Point 1, 2 do not improve the symptom, replace the main PCB.
2-21. E: 57. Damper (Open/Close) simultaneous detection limit switch error (Indoor
unit)
Operation indicator
Timer indicator
Economy indicator
Error code
When the limit switch detects open and close at the
simultaneous.
End
- (03-34) -
5 time flash
7 time flash
Continuous flash
E: 57
Limit switch failure
Shorted connector/wire
Controller PCB failure
2. Troubleshooting with error code