Line Set Routing And Brazing - Scotsman Prodigy ELITE A Series Installation And User Manual

Hide thumbs Also See for Prodigy ELITE A Series:
Table of Contents

Advertisement

MC1448, MC1848, MC2148
Remote Cooled User Manual

Line Set Routing and Brazing

Do not connect the refrigerant tubing until all
routing and forming of the tubing is complete.
Final connections requires brazing, steps must
be performed by an EPA certified type II or higher
technician.
The Lineset of tubing contains a 5/8" diameter liquid
line, and a 1/2" diameter discharge line.
Note: The openings in the building ceiling or wall,
listed in the next step, are the minimum sizes
recommended for passing the refrigerant lines
through.
2. Have the roofing contractor cut a minimum hole for
the refrigerant lines of 1 3/4". Check local codes, a
separate hole may be required for the electrical power
supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while
routing it.
At Condenser:
1. Remove protective plugs from both connections
and vent the nitrogen from the condenser.
2. Remove the tubing access bracket to allow more
room for brazing.
3. Route the lineset tubes to there connection.
4. Clean tubing ends and position into stubs.
Note: Be sure tube and stubs are round, dress with
swage tool if needed.
At Head:
1. Remove the tubing access bracket to allow more
room for brazing.
1. Confirm connection ball valves are fully closed.
2. Remove protective plugs from both connections.
3. Remove caps from access valve connections.
4. Remove cores from access valves.
5. Connect refrigeration hoses to access valves.
6. Connect dry nitrogen source to liquid line
connection.
7. Shorten tubing to correct length, clean ends and
insert them into valve stubs.
Note: Be sure tube and stubs are round, dress with
swage tool if needed.
8. Add heat sink material to ball valve body.
9. Open nitrogen and flow 1 psi nitrogen into liquid
line tube and braze the liquid line and discharge
line tubes to the valve stubs.
10. With nitrogen flowing braze the liquid and
discharge line connections.
At Condenser:
1. Braze the liquid and discharge line connections.
At Head:
1. Remove nitrogen source.
2. Return valve cores to access valves.
3. Connect vacuum pump to both access valves and
evacuate the tubing and head to at least a 300
micron level.
4. Remove vacuum pump and add R-404A to both
tubes to provide a positive pressure.
5. Leak check the all braze connections and repair
any leaks.
6. Open both valves to full open.
Note: The full refrigerant charge is contained in the
receiver of the ice machine.
March 2021
Page 10

Advertisement

Table of Contents
loading

Table of Contents