14.8

Electromagnetic Compatibility EMC

Immunity IEC 61000-6-2, IEC 61000-6-4, IEC 61000-4-2/3/4/5/6/8/12
Electrostatic discharge
Radiated electromagnetic fields
Bursts
Power supply
Data lines
Surges
Common mode
Differential mode
Direct coupling into shield
Conducted disturbances
Damped oscillatory waves
Common mode
Differential mode)
Direct coupling into shield
Emission IEC 61000-6-4, CISPR 11 / 22, IEC 60834-1
RF disturbance emission radiated
Conducted emission
Conducted noise
Insulation Withstand Voltage IEC 60950-1
VF input/output
Power supply
Command input/output
Alarm outputs
G703.1
G703.6 sym.
Impulse Withstand Level 1,2/50µs IEC 60950-1
VF input/output
Digital input/output
Power supply
Command input/output
Alarm outputs
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
14.8 Electromagnetic Compatibility EMC
8 kV (contact discharge)
15 kV (air discharge)
10 V/m, (80 MHz to 2 GHz)
2 kV
2 kV
2 kV (line-to-ground)
1 kV (line-to-line)
2 kV (communication cable)
AC 10 V, 150 kHz to 80 MHz
2.5 kV (line-to-ground)
2.5 kV (line-to-line)
2.5 kV (communication cable)
Limit class A, 20 MHz to 1000 MHz (air discharge)
CISPR class A, power supply and signal cable
IEC 60834-1, 3 mV, 0 Hz to 4 kHz
AC 500 V
AC 3 kV
AC 3 kV
AC 3 kV
AC 500 V
AC 500 V
1 kV
1 kV
5 kV
5 kV
5 kV