ITPC class
RxCmdCnt16
NumTxCmd
NumRxCmd
TpcTxMod
TpcRxMod
Measured values
FerCh1
FerCh2
CarLev
SigNsRat
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
INS
For diagnostics: Received command 16 counters.
INS
Numbers of used binary transmit commands.
Possible values: 0...16
INS
Numbers of used binary receive commands. Possible values:
0...16
ENS
Teleprotection application mode in Transmit direction for each
command.
Possible values:
0: Direct tripping
1: Permissive tripping
ENS
Teleprotection application mode in Receive direction for each
command.
Possible values:
0: Direct tripping
1: Permissive tripping
MV
Frame Error Rate of the communication channel LID-1.
Used in case of a digital communication channel. This attribute is
mapped to BER of DLE.
MV
Frame Error Rate of the communication channel LID-2.
MV
Power of received signal (in dB), used in case of an analogue
communication channel.
MV
Signal to noise ratio (in dB), used in case of analogue communi-
cation channel.
Functional Description