Symbio™ Panel Conversion Kit Contents - Trane Symbio CVRF Installation Instructions Manual

Chiller controller retrofit replacement panel ucp2
Hide thumbs Also See for Symbio CVRF:
Table of Contents

Advertisement

General Information
Remove the existing chiller nameplate on the unit and relocate
to the outside of the new control panel. Important information
is contained on this existing nameplate that must be retained
for future unit servicing. 
If nameplate cannot be removed and relocated, copy
information from old nameplate onto new vinyl nameplate
included in retrofit package.
Symbio™ Panel Conversion Kit
Contents
Each Symbio™ panel conversion kit includes a pre-assembled
control panel with a number of standard features and options
Table 2.
LLID legend and identification
LLID Name
Tracer® Adaptiview™ color display
LON
DAIO
DBI
DHVBI
DRO
HPRO
IGV
Power supply
Pressure sensor
Pressure sensor
Pressure transducer
QRO
Starter module
Starter module power supply
Starter module on sub plate without power supply or LV
PTs
Starter module on sub plate without power supply with
LV PTs
Starter module on sub plate with power supply without
LV PTs
Starter module on sub plate with power supply and LV
PTs
AFD starter nodule on sub plate without power supply
or LV PTs
AFD starter nodule on sub plate with power supply
without LV PTs
Temp sensor
Triac
TWTI
Symbio™ controller
6
installed, wired, bound, and tested, along with some device
LLIDs shipped loose that require field installation and binding.
Before commencing the Symbio™ control retrofit, be sure to
compare the data on the panel nameplate and ordering and
shipping information to the data in the following tables to verify
that the proper Symbio™ components were shipped. The
tables are split into those components that are factory installed
and those that are shipped loose and need to be field installed.
If an inspection of the conversion package reveals damage or
material shortages, be sure to file these claims with the carrier
immediately. Specify the extent of the damage or material
shortages and be sure to notify the appropriate Trane
representative. Do not install a damaged component or panel.
(a)
Description
®
LonTalk
Communications interface for chillers
Dual analog input and output
Dual low voltage binary input
Dual high voltage binary input
Dual relay output
High power relay output
Inlet guide vane stepper actuator
27 Vac to 24 Vdc for bus power supply
Low pressure range, 0 to 50 psia
High pressure range, 0 to 475 psia
Danfoss pressure transducer, 475 PSI 
7/16-20 NUF
Quad relay output
Trane control board, starter module
110 Vac/24 Vdc power supply
Starter sub-panel for unit mount medium voltage
starters
Starter sub-panel for remote mount medium voltage
starters
Starter sub-panel for unit mount low voltage starters 018504220100
Starter sub-panel for remote mount low voltage
starters
Assembly for unit mount UCP2 AFDB, AFDC, and non-
communicating AFDH
Assembly for remote mount UCP2 AFDB, AFDC, and
non-communicating AFDH
Low range temperature sensor
Dual triac output
Triple winding temperature input
Part Number
MOD03183
KIT18458, KIT; ECHELON MODULE FIELD INSTALL
KIT
BRD04875
BRD04873
BRD04874
BRD04878
MOD01401
ACT00680
BRD02102
TDR00733
TDR00734
TDR00735
BRD04879
BRD04877
PWR00147
018504210100
018504330100
018504350100
018504340100
018504370100
SEN02133
BRD04876
MOD02462
MOD02979
CVRF-SVN005C-EN