Trane Symbio CVRF Installation Instructions Manual page 20

Chiller controller retrofit replacement panel ucp2
Hide thumbs Also See for Symbio CVRF:
Table of Contents

Advertisement

Installation
Figure 12. Sample of IPC cable routing
CAB01146
short, male to 2 female
CAB01155
leads to female
Control Panel
To connect the IPC bus to the control panel LLIDs, thread the
bus into the control panel via a knockout or other entry. The
CAB01155 connector has a female plug on one end and four
stripped leads on the other end. Attach the four stripped leads
to the power supply in the control panel.
Figure 13. Connecting the stripped leads to the power
supply
Table 7.
Cables shipped for various options
CAB01146
branch M
2F 500 mm
Standard panel cables
5
Actuator-stepper
Oil protection—full, low
pressure or high pressure
Heat recovery / aux
condenser
Hot gas bypass—electric
actuator
20
CAB01149
short, male to female
Transducer LLID
CAB01147
CAB01148
(a)
to
branch M to
branch M to
2F 1000 mm
3F 500 mm
5
5
1
1
1
1
1
Notes:
R. Red wire for 24 Volts direct current
Bk. Black wire for ground
Bl. Blue wire for IPC+ connection
Gr. Gray wire for IPC- connection
Make sure all devices and LLIDs are connected together in
some way. Use the correct cables so that you don't have any
open plugs when finished. Avoid placing wire ties directly over
plug connectors. This may press on the locking mechanism
and over time the plugs may release.
CAB01149
CAB01150
extension M
extension M
to F 1000 mm
to F 2000 mm
10
9
1
1
1
1
CAB01152
CAB01154
extension M
extension M
extension F to
to leads 1000
to receptacle
mm
1M
2
2
CVRF-SVN005C-EN
CAB01155
leads 1000
mm