Starter Sub-Panel - Trane Symbio CVRF Installation Instructions Manual

Chiller controller retrofit replacement panel ucp2
Hide thumbs Also See for Symbio CVRF:
Table of Contents

Advertisement

Starter Work
c. Drill 3/4-inch or 1-inch hole through panel and starter
cabinet, near top of cabinet, to accommodate wires
from sub-box to starter. Add grommet to hole.
3. Mounting and pre-wiring of components on back panel.
a. Mount starter sub-panel on the back panel.
b. Label components using labels provided.
c. Attach starter module LLID to IPC bus.
Figure 44. Starter sub-panel with PTs, CTs and power
supply
Table 8.
Sub-panel types
Model #
Digit 33
Application
Starter module with plate for
E
medium voltage unit starter
Starter module with plate for low
A
voltage unit starter
Starter module with plate for
F
medium voltage remote starter
Starter module with plate for low
B
voltage remote starter
Starter module with plate for unit
C
AFD
Starter module with plate for
D
remote AFD
34
Part Number
Description
Starter module on sub plate
0185-0421-0100
W/O power supplier, W/O PT
Starter module on sub plate
0185-0433-0100
W/O power supplier, W/ PT
Starter module on sub plate
0185-0422-0100
W/ power supplier, W/O PT
Starter module on sub plate
0185-0435-0100
W/ power supplier, W/ PT
AFD Starter module on sub plate
0185-0434-0100
W/O power supplier, W/O PT
AFD Starter module on sub plate
0185-0437-0100
W/ power supplier, W/O PT

Starter Sub-Panel

The Symbio™ starter module is provided on an assembled
sub-panel that is a direct replacement for the UCP2 starter
module mounted in conventional starters and AFD
applications. The sub panel has three significant options:
– It has the option of a 24 Vdc power supply to be used
on remote mount starters and drives.
– It has the option of pre-installed 600 V or less current
transformers
– It comes in a starter and AFD configuration. The AFD
configuration includes the needed LLIDS for UCP2
AFD control.
Each subpanel It is also provided as standard with a mounting
bracket that allows mounting of factory installed AFD LLIDs or
field installed secondary current transformers or pilot relays
when needed.
A description of the sub-panel's types and uses is below:
Starter
Mount Type
Configuration
Unit mount
MV starter
Unit mount
LV Starter
Remote
MV starter
mount
Remote
LV Starter
mount
AFD starter already
Unit mount
has LV PTs
Remote
AFD starter already
mount
has LV PTs
PTs
Selection FACT/FCOD
STYP/STUN;
TPOT=NONE
STYP/STUN;
TPOT=CPTA,CPTB,CPTC,
CPTD,CPTE,CPTF
STYP/STRE;
TPOT=NONE
STYP/STRE;
TPOT=CPTA,CPTB,CPTC,
CPTD,CPTE,CPTF
STYP/AFUN;
TPOT=NONE,CPTB,CPTC
,CPTD,CPTE,CPTF
STYP/AFRE;
TPOT=NONE,CPTB,CPTC
,CPTD,CPTE,CPTF
CVRF-SVN005C-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents