Lontalk® Option Installation; Communication Option Installation; Wi-Fi Installation - Trane Symbio CVRF Installation Instructions Manual

Chiller controller retrofit replacement panel ucp2
Hide thumbs Also See for Symbio CVRF:
Table of Contents

Advertisement

Installation
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer's
literature for allowable waiting periods for discharge of
capacitors. Verify with a CAT III or IV voltmeter rated per
NFPA 70E that all capacitors have discharged.
WARNING
PPE for Arc/Flash Required!
Failure to wear appropriate PPE could result in death or
serious injury. 
On this unit, if the handle shield is cracked the circuit
breaker could arc/flash when reset. To avoid being
injured, technicians MUST put on all necessary
Personal Protective Equipment (PPE), in accordance
with NFPA70E for arc/flash protection, PRIOR to
entering the starter panel cabinet.
®
LONTALK
Option Installation
Symbio™ 800 system uses a U60 LON module through the
USB connection instead of the LCI-C LLID.
1. Install the U60 LON module (KIT18458, KIT; ECHELON
MODULE FIELD INSTALL KIT) on the DIN rail on the door,
put it at left side of Symbio™ 800.
2. Connect U60 LON module to Symbio™ 800 by USB cable
which is provided with the module Connect this cable to
any one of the four USB ports under the Symbio™ 800
controller.
3. Connect U60 LON module to the BAS system using
shielded cable.
22
Figure 15. LON module
Figure 16. LON wiring, ref. 50712738
OPTIONA L
1A22 SYMBIO800 UNIT CONTROLLE R
4Y2
LTE
MODEM
TRACER
COMMUNICA TIONS
OPTIONAL
Communication Option
Installation
Symbio™ 800 system supports up to 3 wireless interfaces at
same time, these are:
Wi-Fi mobile APP for BAS interface
Air-Fi BACnet via Zigbee for component interface
LTE 4G modem interface for remote communications.

Wi-Fi Installation

Refer to BAS-SVN042*-EN for more information. Mounting
and wiring of Wi-Fi module (MOD03122).
1. Drill a 1.36-inch holes on the top of polycarbonate box,
securely fasten the Wi-Fi module by gasket and nut which
provided by module.
2. Connect Wi-Fi module to Symbio™ 800 by USB cable
which provide by module, plug USB MICRO-B side to
ETHERNET
USB
1
1
2
3
4
1K47
LON
INTERFAC E
CVRF-SVN005C-EN
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents