Parameterization Of The Diagnostics - Siemens SIMATIC Ident RF360R Configuration Manual

Rfid systems
Hide thumbs Also See for SIMATIC Ident RF360R:
Table of Contents

Advertisement

Service and maintenance
8.1 Diagnostics
8.1.8

Parameterization of the diagnostics

With STEP 7 Basic / Professional, you can select which diagnostic interrupt messages you wish
to view. Follow the steps below to deactivate the diagnostic interrupt messages:
"Device view > Device overview > Reader module > General > Module parameters >
Diagnostic messages"
Diagnostic messages
The following settings of the diagnostic messages are available to you:
• None
No further diagnostic data is reported.
• Hard errors
Critical hardware errors/faults are reported by the S7 diagnostics. Extended diagnostic
messages are generated in the case of the following events.
– Hardware fault (memory test)
– Firmware error (checksum)
– Connection interruption
– Fault in power supply
– Short-circuit/break, if supported by hardware
– Firmware update (message at start/end)
• Hard / soft errors
In addition to the hard errors, errors that arise during command processing are also
reported in this case.
Please note that messages triggered by command processing are automatically taken back
after 3 seconds.
Differentiation of diagnostic interrupt messages
With the diagnostic interrupt messages, a distinction is made between incoming and
outgoing diagnostic interrupts.
• Incoming diagnostic interrupt
An event occurs and triggers an alarm.
• Outgoing diagnostic interrupt
The event no longer exits. For transient events - e.g. soft errors, the reset is delayed by 3
seconds.
Further information
You can find detailed information on diagnostics on PROFINET IO in the manual "SIMATIC
PROFINET system description
(https://support.industry.siemens.com/cs/ww/en/view/19292127)".
82
Configuration Manual, 03/2022, C79000-G8976-C629-02
SIMATIC RF360R