Components And Physical Data - Carrier 19XRV Start-Up And Service Instructions

With pic 6 controls danfoss vlt fc102
Table of Contents

Advertisement

Components and Physical Data

19XRV Carrier Danfoss VFD Part Numbers are structured as
shown in Fig. 10 and 11.
Description
19XRV — High Efficiency Semi-Hermetic
Centrifugal Liquid Chiller with
Unit-Mounted VFD
Drive Code
D — Danfoss
Maximum Amp Rating
0588
0658
0745
0800
0990
1120
1260
1460
1670
Compressor Frame
3, 4, 5 — Single-Stage
C, E — Two-Stage
Heat Exchanger Size
3
4
5
6
7
8
FC-102 N560 T4 E54
Product Group
FC-102
Power Rating
N315
N355
N400
N450
N500
N560
N630
N710
N800
N1M0
Input Voltage
T4 — 380-480V AC
T7 — 525-690V AC
Enclosure Type
E54 — IP54 (NEMA 12)
E00 — IP00 (Individual Module Drives for Parallel System)
RFI Filter Option
— RFI Filter, Class A2 (6-pulse)
H2
— Parallel Drive and RFI Filter, Class A2 (6-pulse)
P2
Brake
— No Brake IGBT
X
— Safe Torque Off (STO)
T
Display (LCP)
— No LCP
X
PCB Options
C — Coated PCB
X — Not Coated PCB
19XRV D 0800 4
Fig. 10 — Carrier Part Number for 19XRV Danfoss Drive
H2
T
X
C
Fig. 11 — Example of Danfoss Type Code (TC) Breakdown
6
5
A2
F
Special Order Indicator
– — Standard
S — Special Order
Front End Code
F — Fixed Front End
Options
— 65 kA Breaker, 3% DC Choke
A0
— 100kA Breaker, 3% DC Choke
A1
— 65 kA Breaker, 3% DC Choke, Volt and Ammeter
A2
— 100kA Breaker, 3% DC Choke, Volt and Ammeter
A3
— 65 kA Breaker, 5% DC Choke
B0
— 100 kA Breaker, 5% DC Choke
B1
— 65 kA Breaker, 5% DC Choke, Volt and Ammeter
B2
— 100 kA Breaker, 5% DC Choke, Volt and Ammeter
B3
Line Voltage Code
— 380-400/60
3
— 401-439/60
4
— 440-480/60
5
AX BX CX X XX DX
7
C
X
S009
X
9
D Options
DX — No Option
C Option Software
XX — Standard
C1 Options
X — No Option
C0 Options
CX — No Option
B Options
BX — No Option
A Options
AX — No Option
Language Pack
X — Standard
Software Release
— Software Release Number
SXXX
Adaptation B
X — No Adaptation
Adaptation A
X — Standard Cable Entries
C — Carrier
Mains Option
X — No Mains Option
3 — Mains Disconnect and Fuse
4 — Mains Contactor and Fuses
7 — Fuse
E — Mains Disconnect, Contactor, and Fuses
J — Circuit Breaker and Fuses

Advertisement

Table of Contents
loading

Table of Contents