Physical Data - Carrier 30KAV-ZE Series Installation, Operation And Maintenance Instructions

Liquid chiller with variable speed screw compressor and greenspeed smart technology
Table of Contents

Advertisement

8 - PHYSICAL DATA

8.1 - Physical data
8.1.1 - Physical data of standard units
8.1.1.1 - Units 30KAV-ZE 350 kW - 800 kW
30KAV-ZE
Sound levels
Standard unit
Sound power
(1)
Sound pressure at 10 m
(2)
Sound pressure level at 1 m
Dimensions
Standard unit
Length
Width
Height
Operating weight
(4)
Standard unit
Compressors
Standard unit
Unit + option 329
(3)(6)
Circuit A
Circuit B
Unit minimum part load
(5)
Refrigerant
(4)
Circuit A
Circuit B
Oil
Circuit A
Circuit B
Unit control
Languages
Smart energy metering
Wireless connectivity
Expansion valve
Air heat exchanger
Fans
Standard unit
Unit + option 17
(3)
Quantity
Maximum total air flow
Maximum rotation speed
Water heat exchanger
Water volume
Max. water-side operating pressure without hydraulic
module
Water connections
Standard unit
Connections
Outside tube diameter
Casing paint
(1) In dB ref=10
W, 'A' weighted. Declared noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). Measured in accordance with
-12
ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20µPa, 'A' weighted. Declared noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). For information, calculated from the sound
power Lw(A).
(3) Options: 15=Low noise level ; 15LS=Very low noise level ; 17=Fans motors EC type ; 329=Compressors motors PM type
(4) Values are guidelines only. Refer to the unit name plate.
(5)  For standard conditions. Depending on operating conditions, unit might have a different minimum part load or cycle.
(6) Option 329 is not available on units 0900 to 1300.
46
dB(A)
dB(A)
dB(A)
mm
mm
mm
kg
Quantity
Quantity
%
kg
tCO
e
2
kg
tCO
e
2
l
l
l/s
r/s
l
kPa
inch
mm
Eurovent certified values
350A
400A
450A
500A
95
95
96
98
63
63
64
65
75
75
76
78
4387
4387
5578
5578
2261
2261
2261
2261
2324
2324
2324
2324
4691
4700
5067
5077
06Z twin screw variable speed with AC induction motor and variable frequency
06Z twin screw variable speed with AC permanent magnet motor and variable
1
1
1
1
1
1
1
1
13
13
13
13
R1234ze A2L (GWP=1 following AR5, ODP=0)
49
47
53
56
0,34
0,33
0,37
0,39
50
48
54
57
0,35
0,34
0,38
0,40
Oil for R1234ze. Contact Carrier ERCD for supplying.
27
26
25
23
27
26
25
23
SmartVu™ interface with 7" colour touch screen
 10 languages (DE, EN, ES, FR, IT, NL, PT, TR, TU + one chosen 
Electronic expansion valve
Novation™ micro-channel heat exchanger
Flying Bird™ VI impeller variable speed with AC motor and variable frequency
Flying Bird™ VI impeller variable speed with EC motor
6
6
8
8
35580
35580
47440
47440
16,0
16,0
16,0
16,0
Flooded shell and tube heat exchanger
83
88
96
100
1000
1000
1000
1000
5
5
6
6
141,3
141,3
168,3
168,3
Colour code RAL 7035
550A
600A
650A
99
98
99
66
65
67
78
77
78
6772
6772
7962
2261
2261
2261
2324
2324
2324
5519
5951
6367
drive
frequency drive
1
1
1
1
1
1
13
13
13
64
77
86
0,45
0,54
0,60
65
58
68
0,46
0,41
0,48
20
23
20
20
23
20
by the customer)
Standard feature
Option
drive
10
10
12
59300
59300
71160
16,0
16,0
16,0
115
126
144
1000
1000
1000
Victaulic
type
®
6
6
8
168,3
168,3
219,1
750A
800A
98
100
65
67
77
78
7962
9155
2261
2261
2324
2324
6813
7199
1
1
1
1
12
12
81
87
0,57
0,61
82
88
0,57
0,62
23
20
23
20
12
14
71160
83020
16,0
16,0
165
183
1000
1000
8
8
219,1
219,1

Advertisement

Table of Contents
loading