Commissioning
"DC braking" stopping mode
SIEMENS
3RW44
Menu
ESC
OK
Display mea-
1
1
sured value
select
ESC
OK
Status display
2
select
ESC
OK
3
Settings
select
ESC
OK
OK
1
Parameter
set 1
select
OK
ESC
Motor 1
ESC
Starting
settings
ESC
Stopping
settings
ESC
Stopping mode
Adjustable
DC braking
from ... to
ESC
Stopping time
0 ... 360 s
ESC
DC braking
torque
20 ... 100 %
ESC
Fig. 5-18: "DC braking" stopping mode
5-22
DC braking torque
1
select
OK
2
select
OK
3
select
OK
OK
1
change
OK
2
10 s
change
OK
5
50 %
change
OK
Note
If the "DC braking" function is selected, the "DC brake contactor" function must be
assigned to one output of the soft starter. This output is used to control an external brake
contactor.
Motor
torque (M)
M
Nominal
operation
Motor braking
torque
Stopping time
Stop command
at soft starter
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 02
Time
s