Siemens SIRIUS 3RW44 Manual page 134

Hide thumbs Also See for SIRIUS 3RW44:
Table of Contents

Advertisement

General Technical Data
Type
Power electronics
Rated operational current I
e
Load rating with rated operational current I
• Acc. to IEC and UL/CSA for individual mounting
at 40/50/60 °C, AC-53a
Smallest adjustable operational current I
For the motor overload protection
Power loss
• In operation after completed soft starting with uninterrupted rated
operational current (40 °C) approx.
• During starting with current limit set to 350 %
Permissible rated motor current and starts per hour
• Normal starting (Class 5)
1)
I
- Rated motor current
, starting time 5 s
M
2)
- Starts per hour
1)3)
I
- Rated motor current
, starting time 10 s
M
2)
- Starts per hour
• Normal starting (Class 10)
1)
I
- Rated motor current
, starting time 10 s
M
2)
- Starts per hour
1)3)
I
- Rated motor current
, starting time 20 s
M
2)
- Starts per hour
• Normal starting (Class 15)
1)
I
- Rated motor current
, starting time 15 s
M
2)
- Starts per hour
1)3)
I
- Rated motor current
, starting time 30 s
M
2)
- Starts per hour
• For heavy starting (Class 20)
1)
I
- Rated motor current
, starting time 20 s
M
2)
- Starts per hour
1)3)
I
- Rated motor current
, starting time 40 s
M
2)
- Starts per hour
• For very heavy starting (Class 30)
1)
I
- Rated motor current
, starting time 30 s
M
2)
- Starts per hour
1)3)
I
- Rated motor current
, starting time 60 s
M
2)
- Starts per hour
9-10
e
M
I
(40 °C)
M
1)
Current limit on soft starter set to 350 % I
2)
For intermittent duty S4 with ON period = 70 %, T
operating frequencies do not apply for automatic mode.
3)
Maximum adjustable rated motor current I
3RW44 53
3RW44 54
551
615
A
551/494/438
615/551/489
A
110
123
W
159
186
W
7020
8100
A
551
615
1/h
41
41
A
551
615
1/h
20
20
A
551
615
1/h
20
20
A
551
615
1/h
10
9
A
551
615
1/h
13
13
A
551
615
1/h
6
4
A
551
591
1/h
10
10
A
551
591
1/h
4
2
A
500
525
1/h
6
6
A
500
525
1/h
2
1
.
M
= 40 °C, stand-alone installation vertical. The quoted
u
, dependent on CLASS setting.
M
3RW44 55
3RW44 56
3RW44 57
693
780
880
693/615/551
780/693/615
880/780/693
138
156
176
220
214
250
9500
11100
13100
693
780
880
37
33
22
693
780
880
16
13
8
693
780
880
16
13
8
693
780
880
6
4
0.3
666
723
780
11
9
8
666
723
780
3
1
0.4
633
670
710
7
8
8
633
670
710
1
1
0.4
551
575
600
6
6
6
551
575
600
1
1
1.5