Top Vent - Horizontal Termination - (continued)
Three Elbows
Note: There MUST be a 25% reduction
in total H when using SLP-FLEX Series
(6-5/8 inch) vent except when using
the simple up and out installation. See
Figure 4.8.
CAUTION: The SLP-HRC-SS termination caps are
not approved for use with these models. May lead to
elevated glass temperature that may cause tempered
glass breakage.
Figure 4.12
24
Majestic • JADE32IN, JADE42IN, JADE42IL Installation Manual • 2491-986 Rev. K • 10/18
V
Minimum
1
90° Elbow
1 ft.
305 mm
2 ft.
610 mm
3 ft.
914 mm
*No specific restrictions on this value EXCEPT V
V
Minimum
1
1 ft.
305 mm
2 ft.
610 mm
3 ft.
914 mm
4 ft.
1.2 m
*No specific restrictions on this value EXCEPT V
H
V
2
JADE32IN
H
+ H
Maximum
1
2
6 ft.
1.8 m
10 ft.
3.0 m
12 ft.
3.7 m
14 ft.
4.3 m
H
+ H
MAX. =14 ft. (4.3 m)
1
2
V
+ V
+ H
+ H
MAX. = 40 ft. (12.2 m)
1
2
1
2
+ V
1
2
JADE42IN/JADE42IL
H
+ H
Maximum
1
2
6 ft.
1.8 m
10 ft.
3.0 m
12 ft.
3.7 m
14 ft.
4.3 m
H
+ H
MAX. =14 ft. (4.3 m)
1
2
V
+ V
+ H
+ H
MAX. = 40 ft. (12.2 m)
1
2
1
2
+ V
1
2
2
H
1
V
V
+ V
Minimum
2
1
2
*
*
*
*
*
*
*
*
+ H
+ H
cannot exceed 40 ft. (12.2 m)
1
2
V
V
+ V
Minimum
2
1
2
*
*
*
*
*
*
*
*
+ H
+ H
cannot exceed 40 ft. (12.2 m)
1
2
V
1