Rheem GHE 119-500 Use & Care Manual page 9

Commercial high efficiency water heater
Hide thumbs Also See for GHE 119-500:
Table of Contents

Advertisement

WARNING
!
The water heater must be vented to the
outdoors as described in these instructions.
DO NOT connect this water heater to an existing
Vent or Chimney; it must be vented separately from
all other appliances.
Figure: 3
WARNING
!
Failure to properly vent the water heater to the
outdoors as outlined above and in the following
section can result in unsafe operation of the water
heater causing bodily injury, explosion, fire and
death.
Condensate line must be pitched down at least 1/4"
per foot to properly drain. If this cannot be done or a
very long length of condensate hose is used, you must
increase the condensate hose to a minimum of 1" ID and
place a tee in the line after the condensate neutralizer, to
properly reduce vacuum lock in the drain line (See Figure
2).
Installation
Minimum clearance from combustible material is
0" for the sides, top, and back of this water heater.
This water heater is approved for installation in
an alcove with the required clearances shown in
Figure 4.
WARNING
!
NOTICE: DO NOT use in conjunction with a GFCI.
To avoid the risk of fire, explosion or asphyxiation from
carbon monoxide, NEVER operate this water heater
unless it is properly vented and has an adequate air
supply for proper operation. The vent pipe must overlap
a minimum of ½" on each connection. It is important that
the vent pipe engages fully into any pipe fitting and be
kept in that position until the adhesive has fully cured. DO
NOT drill or punch holes in the plastic pipe or fittings.
Combustible or
non-combustible oors
Required Minimum Access Clearances
9
Combustible or
24"
non-combustible walls
12"
12" Min., recommended 24"
Figure 4
24"
24"