Rheem GHE 119-500 Use & Care Manual page 8

Commercial high efficiency water heater
Hide thumbs Also See for GHE 119-500:
Table of Contents

Advertisement

At a minimum, use 1 1/2" pipe for GHE119/125-500
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of
Based on a 0.60 Specific Gravity Natural Gas; If 1.5 Specific Gravity L.P. Gas is used, multiply capacity by 0.63
Nominal
Internal
Iron Pipe Size
Diameter
Inches
Inches
1/2
.622
3/4
.824
1
1.049
1 1/4
1.380
1 1/2
1.610
2
2.067
2 1/2
2.469
3
3.068
4
4.026
Maximum Pipe Capacity for Installations in Canada,
refer to CAN/CSA B149.1.
For Natural Gas see Tables A.1 to A.17
For Propane (LP) Gas see Tables B.1 to B..12
LEAK TESTING — The water heater and its gas
connections MUST be leak tested at normal oper-
ating pressure before it is placed in operation. Turn
ON the manual gas shut-off valve near the water
heater. Use a soapy water solution to test for gas
leaks at all connections and fittings. Bubbles indi-
cate a gas leak that must be corrected. The water
heater factory connections to the gas valve should
also be leak tested after placing the water heater
in operation.
NEVER use open flame to test for gas leaks, as
bodily injury or property damage could result.
PRESSURE TESTING THE GAS SUPPLY SYSTEM
— The water heater and its manual gas shut-off
valve MUST be disconnected from the gas supply
piping system during any high pressure testing of
that system at pressures in excess of 1/2 psi (14"
w.c. / 3.5 kPa).
The water heater MUST be isolated from the gas
piping system by closing the manual gas shut-off
valve during any pressure testing of the gas supply
piping at pressures equal to or less than 1/2 psi
(14" w.c. / 3.5 kPa).
6. CONDENSATE
This is a condensing high efficiency appliance,
therefore this unit has a condensate removal
system. Condensate is nothing more than water
vapor, derived from the combustion products. This
condensate does have a low pH and condensate
removal must comply with all local codes. It is
very important that the condensate line is sloped
away from and down to a suitable inside drain. If
the condensate outlet on this unit is lower than the
drain, you must use a condensate removal pump.
It is also very important that the condensate line is
not exposed to freezing temperatures, or any other
type of blockage. Plastic tubing should be the only
material used for the condensate line. Steel, brass,
copper, or other metals will be subject to corrosion
Installation
For U.S. Installations
0.5 psig or Less and a Pressure Drop of 0.3 Inch Water Column
10
20
30
40
132
92
73
63
278
190
152
130
520
350
285
245
1,050
730
590
500
1,600
1,100
890
760
3,050
2,100
1,650
1,450
4,800
3,300
2,700
2,300
8,500
5,900
4,700
4,100
17,500
12,000
9,700
8,300
TABLE 3
Length of Pipe, Feet
50
60
70
80
56
50
46
43
115
105
96
90
215
195
180
170
440
400
370
350
670
610
560
530
1,270
1,150
1,050
990
2,000
1,850
1,700
1,600
3,600
3,250
3,000
2,800
7,400
6,800
6,200
5,800
and deterioration. A second vent may be neces-
sary to prevent condensate line vacuum lock if a
long horizontal run is used. Also an increase to 1"
tubing may be necessary.
INSTALLATION OF A CONDENSATE
NEUTRALIZER AND PUMP
(Not Supplied)
CONDENSATION ELBOW ASSEMBLY
Prior to connecting the exhaust vent pipe, the
condensate elbow assembly (supplied, but not
factory installed) must be connected to the ex-
haust pipe on the water heater (See Figure 2).
The free end of the 3 x 3 x 1.5 PVC reducing tee
slip fits over the 3" exhaust pipe on the water
heater. For maximum durability and sealing, use
a high heat silicone sealant appropriate for di-
rect vent appliances (rated for at least 150° F).
Apply a bead of silicone around the inside of
the free end of the reducing tee. Do the same
around the end of the exhaust pipe on the
heater. Push the end of the reducing tee onto
the exhaust pipe as far as the tee allows. The
orientation of the condensate elbow assembly is
critical for proper venting of gas and drainage of
condensate. See Figure 3 for proper final orien-
tation of the assembly.
8
90
100
125
150
40
38
34
31
84
79
72
64
160
150
130
120
320
305
275
250
490
460
410
380
930
870
780
710
1,500
1,400
1,250
1,130
2,600
2,500
2,200
2,000
5,400
5,100
4,500
4,100
175
200
28
26
59
55
110
100
225
210
350
320
650
610
1,050
980
1,850
1,700
3,800
3,500
Figure: 2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ghe 125-500a

Table of Contents