Remote Start Terminal Block; Transfer Switch - Generac Power Systems MAGNUM MLT4250 Owner's Manual

Light tower
Table of Contents

Advertisement

Make sure any problems that caused the main circuit
breaker to trip are corrected before returning the switch
to the ON (I) position.
NOTE: The main circuit breaker interrupts power to the
connection lugs only. The receptacle panel has power
even if the main circuit breaker is in the OFF (O) position.
The receptacle panel main circuit breaker, located next to
the main circuit breaker, will disconnect all power to the
receptacle panel.

Remote Start Terminal Block

The remote start terminal block provides a connection for
installation of a remote start switch which will allow the
unit to be started by a remote dry-contact closure switch.
To locate the remote start terminal block, see
Control
Panel.
Figure 3-20. Remote Start Switch Terminals
1. Before entering Auto mode, verify that the contacts
on any remote switch linked to the unit are OPEN.
If the contacts on a remote switch are closed, the
engine will crank and start when Auto mode is
entered.
2. See
Figure
3-20. Attach the switch leads to the
two unused terminals on the unit's remote start
terminal block (A). For additional information, refer
to
Starting the
Unit—Auto/Remote.

Transfer Switch

When the unit is used as a standby power supply, it must
be equipped with a transfer switch which isolates it from
the utility's distribution system. A transfer switch is
designed to transfer electrical loads from the normal
power source (utility) to the emergency power source
(generator) when normal voltage falls below a prescribed
level. The transfer switch automatically returns the load
back to the normal source when power is restored back
to operating levels.
WARNING
Phase rotation must be compatible.
Incompatible phase rotation could result
in equipment damage, death or serious injury.
Owner's Manual for MLT Light Tower
Main
A
B
C
A
D
E
F
WHITE
002806
GRAY
BLACK
Installation of a transfer switch or other type of remote
starting device is the responsibility of the user. Installation
of such devices must be performed by following all
directions supplied by the manufacturer of the switch. If
attaching the unit to a power supply normally serviced by
a utility company, notify the utility company and check
local and state regulations. Familiarize yourself with all
instructions and warning labels supplied with the switch.
Only a trained and licensed electrician should perform
wiring and connections to unit. Failure to follow proper
installation requirements could result in death, serious
injury, and damage to equipment or property.
(000226a)
A
F
E
Figure 3-21. Transfer Switch Operation
Incoming Utility Power
Emergency Distribution Panel (Generator
Power)
Main Distribution Panel (Utility Power)
Transfer Switch
Power From Generator
Utility Meter
Incoming Utility Power
Normal Utility Power Circuit
Emergency Generator Power Circuit
DANGER
Electrocution. Never connect this unit to the electrical
system of any building unless a licensed electrician
has installed an approved transfer switch. Failure to
do so will result in death or serious injury.
WARNING
Operation
B
C
D
002807
(000150)
(000155)
25

Advertisement

Table of Contents
loading

Table of Contents