Generac Power Systems MAGNUM MLT4250 Owner's Manual page 26

Light tower
Table of Contents

Advertisement

Operation
Figure 3-14. Engine Prestart
5. See
Figure
3-15. The Starting screen will be
displayed. The engine will crank and start running.
Figure 3-15. Controller Starting Screen
6. See
Figure
3-15. The Running screen will display.
NOTE: It may take a few seconds for the engine to run
smoothly and reach its governed operating speed. The
45 second V Detect time delay will start to count down.
22
004532
7. See
Figure
from the Running screen to the generator screen
and then to the engine screen.
004533
Figure 3-17. Generator/Engine Display Screens
8. If the engine does not start after the first cranking
attempt, the engine will pause for 15 seconds to
allow the starter to cool. The LCD window will show
PAUSE. The engine will make two more attempts
to start, for a total of three crank cycles.
9. Should the engine not start and run within three
starting cycles, the LCD window will show SD
START FAIL. The starting sequence may be
repeated after the starter has had a minimum of
two minutes to cool. Press FAULT RESET to clear
the controller. To start the unit, press ENGINE
START.
10. The LCD window will show a steady operating
speed. Temperature will be shown as "0" until the
engine temperature is approximately 100°F (38°C).
Figure 3-16. Run Screen
3-17. The LCD window will then toggle
Owner's Manual for MLT Light Tower
004534
004680
004681