Mdc List Of Alarms - Generac Power Systems MAGNUM MLT4250 Owner's Manual

Light tower
Table of Contents

Advertisement

Operation

MDC List of Alarms

Events
No.
Specification
1
AnInIOM Sd
2
AnInIOM Wrn
Battery Flat (low
3
battery)
4
Binary Input
5
ChrgAlternFail
6
EmergencyStop
7
Engine Temp Sd
8
Engine Temp Wrn
9
Fgen<, >
10
Fuel Level Sd
11
Fuel Level Wrn
12
GCB fail
13
Igen unbl
14
Low BackupBatt
15
Oil Press Sd
16
Oil Press Wrn
17
Overload
18
Overspeed
19
ParamFail
20
PickupFault
21
Sd IOM fail
22
SprinkIActive
23
Start failed
24
Stop fail
25
Vbat
26
Underspeed
27
Vgen<, >
18
Information on
Protection
Binary Output
Type
Available
SD
YES
WRN
YES
SD
YES
CONFIG.
YES
WRN
YES
SD
NO
SD
NO
WRN
YES
SD
YES
SD
YES
WRN
YES
SD
NO
SD
NO
WRN
NO
SD
NO
WRN
YES
SD
YES
SD
YES
NONE
NO
SD
NO
SD
NO
WRN
NO
SD
YES
SD
YES
WRN
YES
SD
YES
SD
YES
Description
Shutdown alarm configurable on the input of IG-IOM/IGS-
PTM.
Warning alarm configurable on the input of IG-IOM/IGS-PTM.
If the controller switches off during starting sequence due to
bad battery condition, it doesn't try to start again and acti-
vates this protection.
Configurable Warning/Shutdown alarms on the inputs of IL-
NT.
Failure of the alternator to charge the battery.
If the red emergency stop switch is pushed or opened, shut-
down is immediately activated.
Water temperature is greater than Sd Water Temp setpoint.
Water temperature is greater than Wrn Water Temp setpoint.
The generator frequency is out of limits given by Gen >f and
Gen <f setpoints.
Fuel level is smaller than Sd Fuel Level setpoint (5%). (Not
available on MLG, MLT or MTT units.)
Fuel level is smaller than Wrn Fuel Level setpoint (15%). (Not
available on MLG, MLT or MTT units.)
Failure of the generator circuit breaker.
The generator current is unbalanced.
RTC backup battery is flat (low).
Oil pressure is smaller than Sd Oil Press setpoint.
Oil pressure is smaller than Wrn Oil Press setpoint.
The load is greater than the value given by Overload setpoint.
The protection comes active if the speed is greater than
Overspeed setpoint.
Wrong checksum of parameters. Happens typically after
downloading new firmware or changing of the parameter. The
controller stays in INIT mode. Check all parameters, write at
least one new parameter.
Failure of the magnetic pick up sensor for speed measure-
ment.
Shutdown alarm in case of lost connection to IOM/IGS-PTM
module.
The protection is active if the output Sprinkler is closed.
Unit did not start.
Unit did not stop.
Battery voltage is out of limits given by Batt Undervolt set-
points.
During starting of the engine, when the RPM reaches the
value of Starting RPM setpoint, the starter is switched off and
the speed of the engine can drop under Start RPM again.
Then the Underspeed protection becomes active. Protection
evaluation starts 5 seconds after startup.
The generator voltage is out of limits given by Gen <V and
Gen <V setpoints.
Owner's Manual for MLT Light Tower