ET9500 Installation and Configuration Guide
2

COMMUNICATION PROTOCOL SETUP

2.1 Collecting ET90000's IP Addresses

Write down the IP Address for each of the ET90000 devices attached to the ET9500.
These addresses will be required for configuration in a later step below.
Note the following:
o
All of the ET90000 devices connected to ET9500 must be on the same IP
subnet.
o
The PC that runs the Web Configurator must be on the same IP subnet. This is
the Web Server used to configure the ET9500.

2.2 Selecting the Desired Field Protocol

ET9500 uses the "S" bank of DIP switches (S0 – S3) to select the Field Protocol.
The default configuration is BACnet/IP (S0-S3 are off).
If you have a different Protocol remove the white label (A0-7, B0-3, S0-3) to access DIP
switches.
NOTE: When setting DIP Switches, please ensure that power to the board is OFF.
See Figure 3 for the switch settings to select BACnet MS/TP, BACnet/IP, Modbus TCP/
IP, Modbus RTU or Metasys N2.
Set the DIP switches to the positions that match the Protocol required.
S0
S1
S2
S3
OFF
S0 - S3 DIP
Switches
ON
Field Protocol
BACnet/IP
BACnet MS/TP
Modbus TCP/IP
Modbus RTU
Metasys N2
Figure 3: Switch Configuration for Field Protocol
S Bank DIP Switch Location
S Bank DIP Switches
S0
S1
S2
Off
Off
Off
On
Off
Off
Off
On
Off
On
On
Off
Off
Off
On
— 6 —
S3
Off
Off
Off
Off
Off