Appendix A.3. Bacnet Ip Settings; Appendix A.4. Setting Up The Et9500 For Bbmd On The Bacnet/Ip Network - Intermatic ET9500 Configuration Manual

Bems interface box
Hide thumbs Also See for ET9500:
Table of Contents

Advertisement

ET9500 Installation and Configuration Guide

Appendix A.3. BACnet IP Settings

On the main Web Configurator screen, update the BACnet details and hit the save icon.
Please note that the BACnet Network default value is 50.

Appendix A.4. Setting up the ET9500 for BBMD on the BACnet/IP Network

The ET9500 is capable of being a BACnet BBMD Client on a BACnet network. When this
function is enabled, other BACnet networks on different subnets and other remote BACnet
networks can access the devices on the particular Subnet that the ET9500 is connected
to. Here are the steps to set up a BACnet BBMD Client:
Create the bdt.ini file. You can get a sample bdt.ini file from Intermatic.
Here is a format of the BDT.ini file to create:
// BBMD IP_Address , BBMD port , BBMD subnet Mask
24.90.48.179 , 47808 , 255.255.255.255
64.80.115.156 , 47808 , 255.255.255.255
The last line of the bdt.ini file should be empty.
On the main Web Configurator screen, set the BACnet BBMD option to enable.
Click on the Diagnostics & Debugging button.
Figure 20: Web Configurator showing setting the network number for BACnet IP
Figure 21: Setting up the ET9500 for BBMD on the BACnet IP Network