Rack Specifications and Recommendations

The SFS 7024 switch is designed to be installed in an existing 19-inch equipment rack or server rack.
The SFS 7024 switch is designed for a four-post server cabinet. It is not designed for a two-post telco
cabinet.
Racks should conform to conventional standards. In the United States, use American National Standards
Institute (ANSI)/Electronic Industries Association (EIA) standard ANSI/EIA-310-D-92, and
International Electrotechnical Commission (IEC) 297

Installing and Routing Cable

Building and electrical codes vary depending on the location. Comply with all code specifications when
Note
planning the site and installing cable.
When running cables to the equipment, consider the following:
Figure 2-2
Assembly 90-Degree Bend Radii
American Wire Gauge (AWG) Size
Cable
24
26
28
Cisco SFS 7024 InfiniBand Server Switch Hardware Users Guide
14
Racks should meet the following mechanical recommendations:
Four-post, 19
rack to facilitate easy maintenance
"
Universal mounting rail hole pattern identified in IEC Standard 297
Mounting holes flush with the rails to accommodate the switch
Use a rack grounding kit and a ground conductor that is carried back to earth or to another suitable
building ground. Ground the equipment rack to earth ground.
Provide enough room to work on the equipment. Clear the work site of any unnecessary materials.
Make sure the equipment will have enough clearance for front and rear access.
Do not run cables where they can be stepped on or rolled over.
Be sure cables are intact with no cuts, bends, or nicks.
Provide proper strain relief for standard IB cables by adhering to the following guidelines:
Cable Bend Radii
Temporary 90-degree bend can never be more than 0.5 inches tighter than the values listed above for
any assembly.
This is the absolute minimum sustained bend radius for each 4X cable AWG size. This measurement
is the distance from the panel to the point where the cable makes a 90-degree bend. In other words,
this number includes the 2" connector stand-off from the panel surface.
4X Bend Radius
5.20 inches
4.80 inches
4.70 inches
Chapter
OL-8794-04