7 Installation
7.9.8
To connect the backup heater power
supply
CAUTION
To guarantee the unit is completely earthed, always
connect the backup heater power supply and the earth
cable.
The backup heater capacity can vary, depending on the indoor unit
model. Make sure that the power supply is in accordance with the
backup heater capacity, as listed in the table below.
Backup
Backup
Power
heater type
heater
supply
capacity
*3V
3 kW
1~ 230 V
*9W
3 kW
1~ 230 V
6 kW
1~ 230 V
6 kW
3~ 230 V
6 kW
3N~ 400 V
9 kW
3N~ 400 V
(a)
Equipment complying with EN/IEC 61000-3-12 (European/
International Technical Standard setting the limits for
harmonic currents produced by equipment connected to
public low-voltage systems with input current >16 A and
≤75 A per phase.).
(b)
This equipment complies with EN/IEC 61000‑3‑11
(European/International Technical Standard setting the
limits for voltage changes, voltage fluctuations and flicker in
public low-voltage supply systems for equipment with rated
current ≤75 A) provided that the system impedance Z
less than or equal to Z
user's supply and the public system. It is the responsibility
of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if
necessary, that the equipment is connected only to a
supply with a system impedance Z
Z
.
max
1 Connect the backup heater power supply. For *3V models, a
double‑pole fuse is used for F1B. For *9W models, a 4‑pole
fuse is used for F1B.
2 If required, modify the connections on terminals X6M and X7M.
Backup heater
Connections to
type
backup heater power
supply
F1B
3 kW 1~ 230 V
(*3V)
L N
L N
F1B
3 kW 1~ 230 V
(*9W)
L
L
N
N
6 kW 1~ 230 V
(*9W)
Installer reference guide
42
Maximum
Z
(Ω)
max
running
current
13 A
13 A
(a)(b)
26 A
15 A
8.6 A
13 A
is
sys
at the interface point between the
max
less than or equal to
sys
Connections to
terminals
X6M
X7M
1 2 3 4
5
6 7 8
X6M
X7M
1 2 3 4
5
6 7 8
Backup heater
Connections to
type
backup heater power
supply
F1B
6 kW 3~ 230 V
(*9W)
L1 L2 L3
L1 L2 L3
F1B
6 kW 3N~ 400 V
(*9W)
L1 L2 L3
L1 L2 L3
9 kW 3N~ 400 V
(*9W)
Special remark for fuses:
Special remark for terminals:
As mentioned on the table above, the connections on the terminals
X6M and X7M need to be changed to configure a backup heater.
Refer to the illustration below as a caution about handling the
terminals.
3 Fix the cable with cable ties to the cable tie mountings.
4 Configure the user interface for the respective power supply.
See
"8.2.2 Quick wizard: Standard" on
During connection of the backup heater, miswiring is possible. To
detect possible miswiring, it is highly recommended to measure the
resistance value of the heater elements. Depending on the different
ERLQ004~008CA + EHVH/X04+08S18+26CB
Connections to
terminals
X6M
X7M
1 2 3 4
5
6 7 8
X6M
X7M
1 2 3 4
5
6 7 8
page 48.