Operation Range; Operation Range: Heating And Cooling - Daikin Altherma EHVH04S18CB3V Installer's Reference Manual

Low temperature split
Table of Contents

Advertisement

14 Technical data
14.8

Operation range

14.8.1

Operation range: Heating and cooling

Space heating and cooling mode (for current models in this manual)
Cooling mode
4~8 kW
A (°C DB)
43
18
10
5
13
22
50
B (°C)
3TW60813-1D
Cooling mode
A
Outdoor temperature
B
Leaving water evaporator temperature
C
Leaving water condensor temperature
Backup heater only operation. No outdoor operation.
Outdoor unit operation is possible if setpoint ≥⁠ 2 5°C.
Operation of outdoor unit is possible, but with possible capacity reduction. If the outdoor temperature <⁠ – ⁠ 2 5°C, the outdoor unit will stop. Indoor
unit and backup heater operation will continue.
Pull-down area.
Remark: In restricted power supply mode, the outdoor unit, booster heater, and backup heater can only operate separately.
(*)
ERLQ units include special equipment (insulation, heater sheet,...) to ensure proper operation in areas with low ambient temperatures and high
humidity conditions. In such conditions, the ERHQ models may experience problems with severe ice buildup on the air-cooled coil. If such
conditions are expected, the ERLQ must be installed instead. These models contain countermeasures (insulation, heater sheet,...) to prevent
freeze-up.
Installer reference guide
106
Heating mode
4~8 kW
A (°C DB)
25
10
0
–15
–20
–25
15 18 25
30
45
50
55
C (°C)
3TW60813-1D
Heating mode
11~16 kW
A (°C DB)
46
10
5
22
B (°C)
3TW60813-1D
ERLQ004~008CA + EHVH/X04+08S18+26CB
11~16 kW
A (°C DB)
35
0
*
–20
–25
15 18 25
55
C (°C)
3TW60813-1D
Daikin Altherma – Low temperature split
4P384973-1A – 2016.02