Appendix D: Intelligent Detector Base Layouts for Legacy Devices

D.1 Wiring a Detector Base
Figure D.1 shows typical wiring of the B710LP or B501 detector base connected to an SLC. An optional RA100Z Remote LED Annun-
ciator is shown connected to the base.
B501 only: For connection of
70
cable shield
Figure D.1 Wiring of the B710LP or B501 Detector Base
NOTE: The B710LP base wiring is identical to the B501, except there is no shield terminal.
SLC
RA100Z
Remote LED
Annunciator
(Optional)
Notifier SLC Wiring Manual — P/N 51253:U5 12/20/2017
Use a female disconnect
to wire the RA100Z (–) to
Terminal 1 (–).
To next device
on SLC