Advertisement

Product Description

1.7 Optional Modules

20
1.6.3 300 Series Intelligent Addressable Devices
Fire•Lite's 300 Series Intelligent Addressable Devices are fully compatible with the
MS-9600 FACP. The devices must be configured for CLIP Mode operation if the
control panel is installed in an existing system with 300 Series devices. The address of
300 Series devices cannot be set above 99. Compatible devices include:
SD300 Photoelectric Detector
SD300T Photoelectric Detector with Thermal Sensor
CP300 Ionization Detector
M300 Monitor Module
M301 Miniature Monitor Module
M302 2-wire Monitor Module
C304 Control/Relay Module
BG-10LX Manual Pull Station
1.6.4 Addressable Device Accessories
End-of-Line Resistor Assembly Fire•Lite P/N R-47K
The 47 kΩ End-of-Line Resistor assembly (P/N: R-47K) is used to supervise the
MMF-300, MDF-300, MMF-301 and CMF-300 module circuits. The 3.9 kΩ End-of-
Line Resistor assembly is used to supervise the MMF-302 module circuit. The resistors
are included with each module.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4-
wire smoke detectors and notification appliances.
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate which is required for use in Canada.
An ELR, which is supplied with each module and fire alarm control panel, is mounted
to the ELR plate. Resistors mounted to the N-ELR plate can be used for the supervision
of a monitor and control module circuit.
The MS-9600 main circuit board includes option module connectors for the following
modules:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter,
alarm and trouble reverse polarity. It includes a disable switch and disable trouble
LED. A jumper on the module is used to select an option which allows the reverse
polarity circuit to open with a system trouble condition if no alarm condition exists.
The module plugs into connectors J10 and J11 which are located near the top center of
the main circuit board. When the 4XTMF module is installed, Jumper JP6, on the main
circuit board, must be cut to allow supervision of the module.
SLC-2 Expander Module
The SLC-2 Expander Module allows expansion of the MS-9600 from one SLC circuit
to two SLC circuits. The module plugs into connector J3 which is located in the lower
right corner of the main circuit board. The wiring for the second SLC connects to
terminals located on the expander module.
DACT-UD Digital Alarm Communicator/Transmitter
The DACT-UD is used to transmit system status to UL-listed Central Station receivers
via the public switched telephone network. All circuitry and connectors are contained
on a compact module which plugs into connector J2, which is located near the bottom
center of the main circuit board.
Optional Modules
MS-9600 PN 51335:E1 2/14/08