Supervising 24 VDC Power
Figure A.1 shows the supervision of a 24VDC circuit using the FCM-1 or FZM-1. Refer to the Device Compatibility Document for com-
patible notification appliances and relays.
Figure A.2 shows an alternate method of supervising a 24VDC circuit.
Notifier SLC Wiring Manual — P/N 51253:U5 12/20/2017
24 VDC Power from
Control Panel or
Power Supply
Power Supervision
Relay
(EOLR-1)
ELR:
(Use 47K with FCM-1
or 3.9K with FZM-1)
Figure A.1 Supervised 24 VDC Circuit
ELR 47K
Power Supervision
Relay
(EOLR-1)
Supervised NAC or IDC
ELR 47K
Figure A.2 Alternate: 2-Address Method of Supervising a 24 VDC Circuit
Supervised NAC or IDC
24 VDC Power from
Control Panel or Power Supply
Last device on the SLC loop
(FCM-1 or FZM-1)
FCM-1
FMM-1