Commissioning instructions

S-Quad Sensor with Strobe - STATES (legacy devices)

The STATE in which the S-Quad sensors operate can be changed from the default factory set STATE to another STATE during commissioning. The environment in which the S-Quad device is installed
will determine what STATE is applicable. # - Factory Default STATE ~ EN54 : Part 7 :2000 * EN54 : Part 5 :2002 ¯ - used in current range
&
The release of control panel software (MCC/MCB equal to or greater than V4.41):
If a non defined STATE is selected during commissioning then the control panel will revert to STATE 0.
The previous release of control panel software (MCC/MCB less than V4.41):
If a non defined STATE is selected during commissioning then the control panel will revert to STATE 15, which means the device is functionally switched OFF.
Dual Optical & Heat sensor variant -
(With Strobe & Speech)
Dual Optical, Heat & CO sensor variant -
(With Speech & Strobe)
Optical & Heat sensor variant -
Heat sensor variant -
(With Speech & Strobe)
Optical senor -
All S-Quad range of sensor sounder devices meet CEA 4021, where applicable, and meet EN54-17:2005 Short circuit isolation plus EN54-18:2005 Input/Output devices for use on the transmission path
of fire detection and alarm systems.
74
Device
LPCB approved STATE
State 0 #
S4-711¯
S4-711-ST
(With Strobe)
State 5
S4-711-VO
(With Speech)
State 8
S4-711-ST-VO
S4-771
(With Sounder)
S4-911
State 0 #
S4-911-ST-VO
State 9
S4-710¯
State 0 #
S4-770
(With Sounder)
S4-720¯
State 0 #
S4-720-ST-VO
State 5
S4-780
(With Sounder)
S4-715¯ State 0
Meets ~ EN54 : Part 7 :2000
* EN54 : Part 5 :2002
Medium optical smoke ~ / Class A1 heat *
Medium optical smoke ~ / Class B heat *
Delayed medium optical smoke ~ / Class A1 heat*
Medium optical smoke ~ / Class A1 heat *
Class A1 heat *
Medium optical smoke / Class A1 heat*
Class A1 heat *
Class B heat *
Medium optical smoke
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.