Empire Comfort Systems MILLIVOLT DVCD FP3-4 Series Installation Instructions Manual page 81

Direct-vent zero clearance gas fireplace heater
Table of Contents

Advertisement

MAINTENANCE & SERVICE - QUALIFIED SERVICE PERSON
NOTICE: If improperly placed, the gasket will prevent the bottom
of the glass frame from contacting the fireplace.
3.
Find the two glass frame clamps on the bottom of the
fireplace.
4.
Pull each clamp down and then over the glass frame.
5.
Place the top ledge of the barrier screen over the top edge of
the glass frame and carefully lower it over the fireplace front.
(Canopy
removed for
clarity)
38712-4-0920
Figure 85
Figure 86
FOR THE INSTALLER
Maintenance Precautions
Installation and repair should be done by a qualified service
person. The fireplace should be inspected before use and at
least annually by a qualified service person. More frequent
cleaning might be required due to excessive lint from carpeting,
bedding material, etc.
Keep burner and control compartment clean.
Examine venting system periodically and replace damaged parts.
Make a periodic visual check of pilot and burners. Clean and
replace damaged parts.
Damaged Fireplace
Do not use this fireplace if any part has been under water.
Immediately call a qualified service technician to inspect the
fireplace and to replace any part of the control system and any
gas control which has been under water.
In the event of a natural disaster (tornado, earthquake, fire, etc.)
have a qualified technician inspect the fireplace for damage or
potential gas leaks. Repair or replace any damaged components
before operating this fireplace.
Annual Inspection
Have the fireplace inspected annually before use.
More frequent inspection and cleaning may be required if the
fireplace is installed in an area exposed to pet hair or dust,
or to excessive lint from new carpeting or bedding materials.
During The Annual Checkup, The Technician Will:
Inspect the pilot (flame safety system) and burner(s) for
proper operation and replace any damaged parts.
Test and measure the flame failure response time of the
flame safety system. It must de-energize the safety shut-off
in no more than 30 seconds.
Vacuum and clean any foreign debris in the firebox that is
not supposed to be there.
Inspect and ensure that the lighting of the main burner
occurs within 4 seconds of the gas valve opening. Visual
inspection should match the information illustrated in the
manual. Inspect primary air openings for blockage.
Check the glass and gasket for proper seal.
Clean Glass with a suitable fireplace glass cleaner. Abrasive
cleaners must not be used. Be careful not to scratch the
glass when cleaning.
Check all latches or other door retention components for
proper operation, tension, and relief mechanisms are free
from obstructions. See Figures 84 and 85.
Check the barrier screen for fit and structural integrity.
See Figure 86.
Inspect the log set (if applicable) and decorative media
(if applicable) for debris or damage.
Freshen up the glowing embers if applicable.
Replace batteries in the remote transmitter and receiver
if applicable.
Inspect the venting and vent termination cap for damage,
corrosion, sooting, or obstruction and correct if present.
Check all accessible gas-carrying tubes, connections,
pipes and other components for leaks.
In addition, clean and inspect the fireplace following any
remodeling work in your home.
Page 81